The protected area is delimited by the revolution enclosure of the same axis as the E.S.E. air terminal and defined by the protection radius corresponding to the different heights h considered (see diagram below):
Lightning rod height

PROTECTION RADIUS OF AIR TERMINALS IONIFLASH AND IONIFLASH BENJAMIN in meters(1) 

(according to standards)

h(m) Level 1 (2) Level 2 (2) Level 3 (2)
2 32 40 44
3 48 59 65
4 65 78 86
5 79 97 107
6 79 97 107
8 79 98 108
10 79 99 109
20 80 102 113
40 77 105 118
60 69 104 120


  If there is a risk for environment (C5 = 10), the protection radius is 

    reduced to 40% according to the interpretation sheet of the NF C 

   17-102 standard from December 2001.

 

  The protection level is determined up to NF C 17-102 standard 

    (enclosure B).

 

 

hn: height of the point of the E.S.E air terminal in relation to the horizontal plane passing through the top of the element to be protected.

Rpn: protection radius of the E.S.E. air terminal for the height under consideration